
The
Freeaire Manual
Specifying
Planning
Installing Wiring
Cooler Controller Commissioning
& Troubleshooting Maintaining
Commissioning
& Troubleshooting
a System
These
two things are closely related, as commissioning is just troubleshooting
that is done right after a system is first installed. Most problems
that occur will make themselves known in the first few days of a new
installation. These are usually easily solved with an adjustment of
one or more of the settings in the Cooler Controller. Sometimes, problems
may not become apparent until humid summer weather arrives, or a big
change in the refrigeration load is made. The installer should try
to anticipate seasonal variations that would affect refrigeration,
and only use settings that will work at anytime of the year.
The
temperature registered by the inside, evaporator, or outside sensor
may be lowered by dipping it into a cup of ice water, or raised by
using the warmth from your hand. This is sometimes useful in determining
whether the Cooler Controller is operating correctly.
Once
the optimum settings for a particular Freeaire installation have been
arrived at, there should be no need for further changes.
Review operation,
user menu adjustments, and maintenance procedures with owner or manager.
Stress close monitoring and possible need for adjustment during start-up
period.
SYMPTOM: Temperature in walk-in is
too cold or too warm. POSSIBLE
CAUSE#1:
The LOW LIMIT setting of the Cooler Controller is too low or too high.
SOLUTION: Adjust to a lower or higher setting. Access the User
Menu by holding down all three white buttons for 5 seconds. When the
LOW LIMIT setting is displayed, use the + or - button to change the
setting. Go
to Cooler Controller: User Menu: Low Limit
POSSIBLE
CAUSE #2: The
inside temperature sensor has failed. SOLUTION
#2: Test
the sensor to determine its accuracy. (Ice water should read 32-33°F
or 0°C.) Replace
if necessary.
POSSIBLE
CAUSE #3: The
compressor system has failed. SOLUTION
#3: Have a refrigeration technician check out its operation.
SYMPTOM:
Condensation forms on the outside of the
reach-in doors during humid weather. CAUSE: The
door heaters are not energized. SOLUTION #1: Switch on the
DOOR HEATERS toggle switch at the Cooler Controller. Check to see
that the door heater circuit breaker is closed in the main electrical
panel. Also check to see that the toggle switches on the door frames
themselves are switched on.
SOLUTION
#2: Adjust the HUMIDISTAT to a lower setting. Go
to Wiring: Low Voltage Wiring- Humidistat
SYMPTOM: Frost build-up on the evaporator
coils. POSSIBLE CAUSE #1: Incorrect evaporator temperature
sensor placement. The sensor is not located in the last part of the
evaporator coils to be completely defrosted and the defrost cycle
is ending too soon. SOLUTION #1: Re-position the sensor to
that part of the coils that stays frosted up. In a cooler, if there
is one sensor for two or more evaporator fan units, the sensor may
have to be moved to the unit that is most frost-prone. As the evaporator
coils may be clogged with ice in the place where a sensor needs to
be re-positioned, note the spot where there is the greatest accumulation
of ice. Take a large slotted screwdriver and heat the tip with a propane
torch. Gently insert the screwdriver into the ice so that a hole is
melted out between two fins and right next to a refrigerant pipe.
Reheat the screwdriver as necessary to deepen and enlarge the hole
to fully insert the sensor into the ice. Secure the sensor wire so
that the sensor will not fall out of the hole when the ice is melted.
Go
to Wiring: Evaporator Sensor.
Begin a defrost cycle by accessing the Installer Menu. Go
to Cooler Controller: Installer Menu: Start Defrost Now.
In a cooler, this will switch the evaporator fans on and switch the
compressor off until the evaporator sensor(s) indicate(s) a temperature
equal to 1 degree less than the inside temperature and the defrost
period ends. In a freezer, this will stop the evaporator fans and
energize the electric defrost heaters. Once the defrost period ends,
make sure that there is no ice left. If there is ice remaining, move
the evaporator sensor again to that spot and begin another defrost
cycle.
POSSIBLE
CAUSE #2: The maximum allowable evaporator temperature setting
to end defrost is too low, ending the defrost cycle prematurely. SOLUTION
#2: The MAX
EVAP TEMP TO END DEFROST
setting should be adjusted to a higher temperature.
Go
to Cooler Controller: Installer Menu: Max Evap Temp.
POSSIBLE
CAUSE #3: The defrost period is "maxed out on time",
which has ended the defrost cycle before the evaporator temperature
could end it. There will be a message in the display window reading
"MAX TIME ENDED LAST DEFROST" if this is the case. SOLUTION
#3:
Raise the MAX TIME TO END DEFROST setting in the Installer Menu to
a higher number.
Go
to Cooler Controller: Installer Menu: Max Time to End Defrost.
POSSIBLE
CAUSE #4: Variation over time of the place of where ice on the
coils forms. SOLUTION #4: The EXTRA
DEFROST TIME
setting should be adjusted to a higher number of minutes. Go
to Cooler Controller: Installer Menu: Extra Defrost Time.
POSSIBLE
CAUSE #5: Too much time between defrost cycles. The ice would
have all formed completely since the last defrost cycle. SOLUTION
#5: The COMP
OP TO START DEFROST
setting should be adjusted to a fewer number of hours. Go
to Cooler Controller: Installer Menu: Comp Op to Start Defrost.
POSSIBLE
CAUSE #6: The
evaporator temperature sensor has failed. SOLUTION
#6: Test
the sensor to determine its accuracy. (Ice water should read 32-33°F.)
Replace
if necessary.
SYMPTOM:
The defrost cycle lasts too long, allowing the
walk-in too get too warm. POSSIBLE CAUSE #1: Too much extra
defrost time. SOLUTION #1: The EXTRA
DEFROST TIME
setting should be adjusted to a lower number of minutes. Go
to Cooler Controller: Installer Menu: Extra Defrost Time.
POSSIBLE CAUSE #2: Too high a maximum temperature to end defrost.
SOLUTION #2: The MAX
EVAP TEMP TO END DEFROST
setting should be adjusted to a lower temperature. Go
to Cooler Controller: Installer Menu: Max Evap Temp.
SYMPTOM:
The Cooler Controller behaves erratically
or gets "stuck" and can't be adjusted. POSSIBLE
CAUSE: This
could happen during a bad thunderstorm or extreme voltage surge. SOLUTION:
"REBOOT" the controller by switching the first switch on the left
(COOLER CONTROLLER) OFF and then ON again. Check the settings in both
the User and Installer menus, and re-enter any incorrect settings.
SYMPTOM:
The Cooler Controller's display window has
the following blinking message: MEMORY FAULT CHECK ADJST MODE.
POSSIBLE
CAUSE: If
there has been a voltage surge, one or more of the custom settings
(i.e. not default settings) may have been lost from the Cooler Controlleršs
memory and the above slowly blinking message will appear. Also any
other window scrolled to or accessed through the User Menu will continue
to blink until the Installer menu is accessed. Meanwhile, the default
settings will be operative. SOLUTION: Enter the User and the
Installer Menus and re-enter any incorrect settings. If you are still
having problems: contact us here at R.H. Travers Company at 802-496-5205
and we will try to come up with a solution.
SYMPTOM:
Condensation drips from the exhaust or intake damper housings during
hot, humid weather.
CAUSE:
There are no summer plugs are not in place and air is leaking around
the dampers.
SOLUTION: Install and adjust
the summer plugs or cap to insure an airtight fit. Rotating the plugs
as they are inserted usually results in a very snug fit.
SYMPTOM:
The amount of outside air coming into the walk-in is noticeably less
than before. CAUSE
#1:
The filter is dirty. SOLUTION
#1:
Replace the filter. Go to Catalog
of Options: Filter.
CAUSE
#2:
The exhaust fan is not operating . SOLUTION
#2:
Check electrical connections. Go into the Installer Menu of the Cooler
Controller and test outside air system operation in OUTPUT TESTING.
SYMPTOM:
The
bottom of the walk-in is colder than the
top, perhaps causing freezing. CAUSE
#1:
The circulating fan is not operating when the evaporator fans aren't.
SOLUTION
#1:
Check electrical connections.
Go into the Installer Menu of the Cooler Controller and test circulating
fan operation in OUTPUT TESTING. Go
to Cooler Controller: Installer Menu: Output Testing.
CAUSE
#2:
The (upflow) circulating fan pipe is blocked. SOLUTION
#2:
Remove blackage.
SYMPTOM:
The
Outside Air System runs at the same time as the compressor and evaporator
fans. CAUSE:
The refrigerating load is too great for the outside air fans at this
outside temperature, so the compressor has come on to help out until
the walk-in cools down.
THIS IS NOT A PROBLEM!
SOLUTION:
None needed.
Specifying
Planning
Installing Wiring
Cooler Controller Commissioning
& Troubleshooting Maintaining